Cogeneratori-gas-natural
Biogas cogenerators
Model Power introduced (kW) Electrical power [kWe] Electrical efficiency % Radiator thermal power [kW] Fumes-cooling thermal power 180° [kW] Total efficiency % Generator voltage (V)
100 247 99 40.5 246 - 79.5 400
250 637 249 39.1 134 129 85.4 400
400 941 400 42.5 201 197 84.8 400
530 1302 526 40.4 313 243 83.3 400
640 1589 634 40.0 389 292 83.6 400
850 2016 844 41.9 497 348 83.7 400
1050 2606 1063 40.8 626 479 82.5 400
1570 3741 1560 41.7 840 815 85.9 400
2000 4762 2000 42.0 1050 1035 85.8 400

The Challenger One Cogeneration Units are equipped with

  • Insulated SEKO Challenger container, complete with ventilation system and soundproofing 65 dB(A) at 10 m
  • Electricity generating set consisting of gas engine with heat recovery from:
  • first stage intercooler; oil; engine cooling water (optional fume heat recovery)
  • Gas train complete with dedicated blower
  • Silencer in stainless steel 65 dB(A) at 10 m complete with catalyst
  • Gas leak supervision system
  • Fume development supervision system
  • Emergency electric radiator for engine block cooling
  • Heat exchanger for use of heat inside the plant (85°C)
  • Lubricating oil top-up auxiliary tank complete with electropump for quick oil change
  • Biogas cooling and dehumidification system
  • Synchronous alternator complete with power board with UTF counter and network protection
  • Control and command panel complete with automatic synchronisation system